181.400—Where required.
(a)
The following spaces must be equipped with a fixed gas fire extinguishing system, in compliance with § 181.410, or other fixed fire extinguishing system specifically approved by the Commandant, except as otherwise allowed by paragraph (b) of this section:
(4)
A space containing machinery powered by gasoline or other fuels having a flash point of 43.3 °C (110 °F) or lower;
(5)
A space containing a fuel tank for gasoline or any other fuel having a flash point of 43.3 °C (110 °F) or lower;
(6)
A space containing combustible cargo or ship's stores inaccessible during the voyage (in these types of spaces only carbon dioxide, and not Halon, systems will be allowed);
(8)
A storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater).
(b)
Alternative system types and exceptions to the requirements of paragraph (a) of this section are:
(1)
A fixed gas fire extinguishing system, which is capable of automatic discharge upon heat detection, may only be installed in a normally unoccupied space with a gross volume of not more than 170 cubic meters (6,000 cubic feet);
(2)
A pre-engineered fixed gas fire extinguishing system must be in compliance with § 181.420 of this part and may only be installed in a normally unoccupied machinery space, a paint locker, or a storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater), with a gross volume of not more than 57 cubic meters (2,000 cubic feet);
(3)
A B-II portable fire extinguisher installed outside the space may be substituted for a fixed gas fire extinguishing system in a storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater) or a paint locker, with a volume of not more that 5.7 cubic meters (200 cubic feet);
(4)
A space which is so open to the atmosphere that a fixed gas fire extinguishing system would be ineffective, as determined by the cognizant OCMI, is not required to have a fixed gas fire extinguishing system; and
(5)
Where the amount of carbon dioxide gas required in a fixed fire extinguishing system can be supplied by one portable extinguisher or a semiportable extinguisher, such an extinguisher may be used subject to the following:
(ii)
The applicator shall be installed in a fixed position so as to discharge into the space protected; and
(c)
The following spaces must be equipped with a fire detecting system of an approved type that is installed in accordance with § 76.27 in subchapter H of this chapter, except when a fixed gas fire extinguishing system that is capable of automatic discharge upon heat detection is installed or when the space is manned:
(4)
A space containing machinery powered by gasoline or any other fuels having a flash point of 43.3 °C (110 °F) or lower; and
(5)
A space containing a fuel tank for gasoline or any other fuel having a flash point of 43.3 °C (110 °F) or lower.
(d)
All griddles, broilers, and deep fat fryers must be fitted with a grease extraction hood in compliance with § 181.425.
(e)
Each overnight accommodation space on a vessel with overnight accommodations for passengers must be fitted with an independent modular smoke detecting and alarm unit in compliance with § 181.450.
(f)
An enclosed vehicle space must be fitted with an automatic sprinkler system that meets the requirements of § 76.25 in subchapter H of this chapter; and
(1)
A fire detecting system of an approved type that is installed in accordance with § 76.27 in subchapter H of this chapter; or
(2)
A smoke detecting system of an approved type that is installed in accordance with § 76.33 in subchapter H of this chapter.
(g)
A partially enclosed vehicle space must be fitted with a manual sprinkler system that meets the requirements of § 76.23 in subchapter H of this chapter.
[CGD 85-080, 61 FR 982, Jan. 10, 1996, as amended at 62 FR 51358, Sept. 30, 1997; USCG-1999-6216, 64 FR 53228, Oct. 1, 1999]