3285.402—Ground anchor installations.
(a) Ground anchor certification and testing.
Each ground anchor must be manufactured and provided with installation instructions, in accordance with its listing or certification. A nationally recognized testing agency must list, or a registered professional engineer or registered architect must certify, the ground anchor for use in a classified soil (refer to § 3285.202 ), based on a nationally recognized testing protocol, or a professional engineer or registered architect must certify that the ground anchor is capable of resisting all loads in paragraph (b) of this section for the soil type or classification.
(b) Specifications for tie-down straps and ground anchors—
(1) Ground anchors.
Ground anchors must be installed in accordance with their listing or certification, be installed to their full depth, be provided with protection against weather deterioration and corrosion at least equivalent to that provided by a coating of zinc on steel of not less than 0.30 oz./ft. 2 of surface coated, and be capable of resisting a minimum ultimate load of 4,725 lbs. and a working load of 3,150 lbs., as installed, unless reduced capacities are noted in accordance with note 11 of Table 1 to this section or note 12 of Tables 2 and 3 to this section. The ultimate load and working load of ground anchors and anchoring equipment must be determined by a registered professional engineer, registered architect, or tested by a nationally recognized third-party testing agency in accordance with a nationally recognized testing protocol.
(2) Tie-down straps.
A 1 1/4 inch x 0.035 inch or larger steel strapping conforming to ASTM D 3953—97, Standard Specification for Strapping, Flat Steel and Seals (incorporated by reference, see § 3285.4 ), Type 1, Grade 1, Finish B, with a minimum total capacity of 4,725 pounds (lbs.) and a working capacity of 3,150 pounds (lbs.) must be used. The tie-down straps must be provided with protection against weather deterioration and corrosion at least equivalent to that provided by a coating of zinc on steel of not less than 0.30 oz./ft. 2 of surface coated. Slit or cut edges of coated strapping need not be zinc coated.
(i)
No greater than the spacing shown in Tables 1 through 3 to this section and Figures A and B to this section; or
(ii)
Designed by a registered engineer or architect, in accordance with acceptable engineering practice and the requirements of the MHCSS for any conditions that are outside the parameters and applicability of the Tables 1 through 3 to this section.
(2)
The requirements in paragraph (c) of this section must be used to determine the maximum spacing of ground anchors and their accompanying anchor straps, based on the soil classification determined in accordance with § 3285.202 :
(i)
The installed ground anchor type and size (length) must be listed for use in the soil class at the site and for the minimum and maximum angle permitted between the diagonal strap and the ground; and
(ii)
All ground anchors must be installed in accordance with their listing or certification and the ground anchor manufacturer installation instructions; and
(iii)
If required by the ground anchor listing or certification, the correct size and type of stabilizer plate is installed. If metal stabilizer plates are used, they must be provided with protection against weather deterioration and corrosion at least equivalent to that provided by a coating of zinc on steel of not less than 0.30 oz./ft.2 of surface coated. Alternatively, ABS stabilizer plates may be used when listed and certified for such use.
(3) Longitudinal anchoring.
Manufactured homes must also be stabilized against wind in the longitudinal direction in all Wind Zones. Manufactured homes located in Wind Zones II and III must have longitudinal ground anchors installed on the ends of the manufactured home transportable section(s) or be provided with alternative systems that are capable of resisting wind forces in the longitudinal direction. See Figure C to § 3285.402 for an example of one method that may be used to provide longitudinal anchoring. A professional engineer or registered architect must certify the longitudinal anchoring method or any alternative system used as adequate to provide the required stabilization, in accordance with acceptable engineering practice.
Code of Federal Regulations
Code of Federal Regulations
Code of Federal Regulations
283
Code of Federal Regulations
Code of Federal Regulations
Code of Federal Regulations
284
Code of Federal Regulations
Nominal floor width, single section/multi-section | Max. heightfrom ground to diagonal strap attachment | I-beam spacing82.5 in. | I-beamspacing99.5 in. |
---|---|---|---|
12/24 ft. 144 in. nominal section(s) | 25 in | 14 ft. 2 in | N/A. |
33 in | 11 ft. 9in | N/A. | |
46 in | 9 ft. 1in | N/A. | |
67 in | N/A | N/A. | |
14/28 ft. 168 in. nominal section(s) | 25 in | 18 ft. 2in | 15 ft. 11 in. |
33 in | 16 ft. 1 in | 13 ft. 6 in. | |
46 in | 13 ft. 3 in | 10 ft. 8in. | |
67 in | 10 ft. 0 in | N/A. | |
16/32 ft. 180 in. to 192 in. nominal section(s) | 25 in | N/A | 19 ft. 5in. |
33 in | 19 ft. 0 in | 17 ft. 5 in. | |
46 in | 16 ft. 5 in | 14 ft. 7 in. | |
67 in | 13 ft. 1 in | 11 ft. 3 in. |
Code of Federal Regulations
Nominal floor width, single section/multi-section | Max. height from ground to diagonal strap attachment | Near beam method I-beam spacing | Second beam method I-beam spacing | ||
---|---|---|---|---|---|
82.5 in. | 99.5 in. | 82.5 in. | 99.5 in. | ||
12 ft/24 ft. 144 in. nominal section(s) | 25 in | 6 ft. 2 in | 4 ft. 3 in | N/A | N/A |
33 in | 5 ft. 2 in | N/A | N/A | N/A | |
46 in | 4 ft. 0 in | N/A | N/A | N/A | |
67 in | N/A | N/A | 6 ft 1 in | 6 ft 3 in | |
14 ft/28 ft. 168 in. nominal section(s) | 25 in | 7 ft. 7 in | 6 ft. 9 in | N/A | N/A |
33 in | 6 ft. 10 in | 5 ft. 9 in | N/A | N/A | |
46 in | 5 ft. 7 in | 4 ft. 6 in | N/A | N/A | |
67 in | 4 ft. 3 in | N/A | N/A | N/A | |
16 ft/32 ft. 180 in. to 192 in. nominal section(s) | 25 in | N/A | 7 ft. 10 in | N/A | N/A |
Code of Federal Regulations
286
|
|||||
33 in | 7 ft. 6 in | 7 ft. 2 in | N/A | N/A | |
46 in | 6 ft. 9 in | 6 ft. 0 in | N/A | N/A | |
67 in | 5 ft. 4 in | 4 ft. 7 in | N/A | N/A |
Code of Federal Regulations
Nominal floor width, single section/multi-section | Max. height from ground to diagonal strap attachment | Near beam method I-beam spacing | Second beam method I-beam spacing | ||
---|---|---|---|---|---|
82.5 in. | 99.5 in. | 82.5 in. | 99.5 in. | ||
12 ft./24 ft. 144 in. nominal section(s) | 25 in | 5 ft. 1 in | N/A | N/A | N/A |
33 in | 4 ft. 3 in | N/A | N/A | N/A | |
46 in | N/A | N/A | N/A | N/A | |
67 in | N/A | N/A | N/A | N/A | |
14 ft./28 ft. 168 in. nominal section(s) | 25 in | 6 ft. 2 in. | 5 ft. 7 in | N/A | N/A |
33 in | 5 ft. 8 in | 4 ft. 9 in | N/A | N/A | |
46 in | 4 ft. 8 in | N/A | N/A | N/A | |
67 in | N/A | N/A | N/A | N/A | |
16 ft./32 ft. 180 in. to 192 in. nominal sections | 25 in | N/A | 6 ft. 3 in | N/A | N/A |
33 in | 6 ft. 1 in | 5 ft. 11 in | N/A | N/A | |
46 in | 5 ft. 7 in | 5 ft. 0 in | N/A | N/A | |
67 in | 4 ft. 5 in | N/A | N/A | N/A |
Code of Federal Regulations
Code of Federal Regulations
287