431.87—Energy conservation standards and their effective dates.
(a)
Each commercial packaged boiler manufactured on or after January 1, 1994, and before March 2, 2012, must meet the following energy efficiency standard levels:
(1)
For a gas-fired packaged boiler with a capacity (rated maximum input) of 300,000 Btu/h or more, the combustion efficiency at the maximum rated capacity must be not less than 80 percent.
(2)
For an oil-fired packaged boiler with a capacity (rated maximum input) of 300,000 Btu/h or more, the combustion efficiency at the maximum rated capacity must be not less than 83 percent.
(b)
Each commercial packaged boiler listed in Table 1 to § 431.87 and manufactured on or after the effective date listed in Table 1 of this section, must meet the applicable energy conservation standard in Table 1.
Equipment type | Subcategory | Size category(input) | Efficiency level—Effective date:March 2, 2012 * |
---|---|---|---|
Hot Water Commercial Packaged Boilers | Gas-fired | ≥300,000 Btu/h and ≤2,500,000 Btu/h | 80.0% ET |
Hot Water Commercial Packaged Boilers | Gas-fired | >2,500,000 Btu/h | 82.0% EC |
Hot Water Commercial Packaged Boilers | Oil-fired | ≥300,000 Btu/h and ≤2,500,000 Btu/h | 82.0% ET |
Hot Water Commercial Packaged Boilers | Oil-fired | >2,500,000 Btu/h | 84.0% EC |
Steam Commercial Packaged Boilers | Gas-fired—all, except natural draft | ≥300,000 Btu/h and ≤2,500,000 Btu/h | 79.0% ET |
Steam Commercial Packaged Boilers | Gas-fired—all, except natural draft | >2,500,000 Btu/h | 79.0% ET |
Steam Commercial Packaged Boilers | Gas-fired—natural draft | ≥300,000 Btu/h and ≤2,500,000 Btu/h | 77.0% ET |
Steam Commercial Packaged Boilers | Gas-fired—natural draft | >2,500,000 Btu/h | 77.0% ET |
Steam Commercial Packaged Boilers | Oil-fired | ≥300,000 Btu/h and ≤2,500,000 Btu/h | 81.0% ET |
Steam Commercial Packaged Boilers | Oil-fired | >2,500,000 Btu/h | 81.0% ET |
* Where EC is combustion efficiency and ET is thermal efficiency as defined in § 431.82 . |
(c)
Each commercial packaged boiler listed in Table 2 to § 431.87 and manufactured on or after the effective date listed in Table 2 of this section, must meet the applicable energy conservation standard in Table 2.
Equipment type | Subcategory | Size category (input) | Efficiency level—Effective date: March 2, 2022 * |
---|---|---|---|
Steam Commercial Packaged Boilers | Gas-fired—natural draft | ≥300,000 Btu/h and ≤2,500,000 Btu/h | 79.0% ET |
Steam Commercial Packaged Boilers | Gas-fired—natural draft | >2,500,000 Btu/h | 79.0% ET |
* Where EC is combustion efficiency and ET is thermal efficiency as defined in § 431.82 . |