230.36—Hydrostatic testing of boilers.
(a) Time of test.
The locomotive owner and/or operator shall hydrostatically test every boiler at the following times:
(b) Method of testing.
The metal temperature of the boiler shall be between 70 degrees Fahrenheit and 120 degrees Fahrenheit each time it is subjected to any hydrostatic pressure. Hydrostatic testing required by these rules shall be conducted at 25 percent above the MAWP.
(c) Internal inspection.
An internal inspection of the boiler shall be conducted following any hydrostatic test where the pressure exceeds MAWP.