195.205—Repair, alteration and reconstruction of aboveground breakout tanks that have been in service.
(a)
Aboveground breakout tanks that have been repaired, altered, or reconstructed and returned to service must be capable of withstanding the internal pressure produced by the hazardous liquid to be stored therein and any anticipated external loads.
(b)
After October 2, 2000, compliance with paragraph (a) of this section requires the following for the tanks specified:
(1)
For tanks designed for approximately atmospheric pressure constructed of carbon and low alloy steel, welded or riveted, and non-refrigerated and tanks built to API Standard 650 or its predecessor Standard 12C, repair, alteration, and reconstruction must be in accordance with API Standard 653.
(2)
For tanks built to API Specification 12F or API Standard 620, the repair, alteration, and reconstruction must be in accordance with the design, welding, examination, and material requirements of those respective standards.
(3)
For high pressure tanks built to API Standard 2510, repairs, alterations, and reconstruction must be in accordance with API 510.
[Amdt. 195-66, 64 FR 15935, Apr. 2, 1999]