180.519—Periodic retest and inspection of tank cars other than single-unit tank car tanks.

Retest Table 1
Specification Retest interval—years Minimum Retestpressure—psig Pressure relief valvepressure—psig
Tank Pressure relief devices d Tank hydrostaticexpansion c Tank air test Start-to-discharge Vapor tight
DOT 27 5 2 500 100 375 300
106A500 5 2 500 100 375 300
106A500X 5 2 500 100 375 300
106A800 5 2 800 100 600 480
106A800X 5 2 800 100 600 480
106A800NCI 5 2 800 100 600 480
107A * * * * d5 a2 (b) None None None
110A500-W 5 2 500 100 375 300
110A600-W 5 2 600 100 500 360
110A800-W 5 2 800 100 600 480
110A1000-W 5 2 1,000 100 750 600
BE-27 5 2 500 100 375 300
Notes:
Code of Federal Regulations 1175
a If DOT 107A * * * * tanks are used for transportation of flammable gases, one rupture disc from each car must be burst at the interval prescribed. The sample disc must burst at a pressure not exceeding the marked test pressure of the tank and not less than 70 percent of the marked test pressure. If the sample disc does not burst within the prescribed limits, all discs on the car must be replaced.
b The hydrostatic expansion test pressure must at least equal the marked test pressure.
c See § 180.519(b)(1) .
d Safety relief valves of the spring-loaded type on tanks used exclusively for fluorinated hydrocarbons and mixtures thereof which are free from corroding components may be retested every 5 years.
[Amdt. 180-8, 60 FR 49079, Sept. 21, 1995, as amended by Amdt. 179-50, 61 FR 33257, June 26, 1996; 65 FR 58633, Sept. 29, 2000; 66 FR 45187, 45392, Aug. 28, 2001; 68 FR 75765, Dec. 31, 2003]