178.275—Specification for UN Portable Tanks intended for the transportation of liquid and solid hazardous materials.

(a) In addition to the requirements of § 178.274, this section sets forth definitions and requirements that apply to UN portable tanks intended for the transportation of liquid and solid hazardous materials.
(c) Service equipment. (1) In addition to the requirements specified in § 178.274, for service equipment, all openings in the shell, intended for filling or discharging the portable tank must be fitted with a manually operated stop-valve located as close to the shell as reasonably practicable. Other openings, except for openings leading to venting or pressure relief devices, must be equipped with either a stop-valve or another suitable means of closure located as close to the shell as reasonably practicable.
(d) Bottom openings. (1) Certain hazardous materials may not be transported in portable tanks with bottom openings. When the applicable T code or portable tank special provision, as referenced for materials in the § 172.101 Table of this subchapter, specifies that bottom openings are prohibited, there must be no openings below the liquid level of the shell when it is filled to its maximum permissible filling limit. When an existing opening is closed, it must be accomplished by internally and externally welding one plate to the shell.
(3) When required for certain hazardous materials by the applicable T code or portable tank special provision specified for a hazardous material in the § 172.101 Table of this subchapter, portable tanks must have a pressure relief device consistent with the requirements of this subchapter. Except for a portable tank in dedicated service that is fitted with an approved relief device constructed of materials compatible with the hazardous material, the relief device system must include a frangible disc preceding (such as, between the lading and the reclosing pressure relief device) a reclosing pressure relief device. A pressure gauge or suitable tell-tale indicator for the detection of disc rupture, pin-holing or leakage must be provided in the space between the frangible disc and the pressure relief device to allow the portable tank operator to check to determine if the disc is leak free. The frangible disc must rupture at a nominal pressure 10% above the start-to-discharge pressure of the reclosable pressure relief device.
Where:
Q = minimum required rate of discharge in cubic meters of air per second (m3/s) at conditions: 1 bar and 0 °C (273 °K);
F = for uninsulated shells: 1; for insulated shells: U(649−t)/13.6 but in no case is less than 0.25
Where:
U = thermal conductance of the insulation, in kW m−2K−1, at 38 °C (100 °F); and t = actual temperature of the hazardous material during filling (in °C) or when this temperature is unknown, let t = 15 °C (59 °F). The value of F given in this paragraph (i)(2)(i)(A) for insulated shells may only be used if the insulation is in conformance with paragraph (i)(2)(iv) of this section;
A = total external surface area of shell in square meters;
Z = the gas compressibility factor in the accumulating condition (when this factor is unknown, let Z equal 1.0);
T = absolute temperature in Kelvin ( °C 273) above the pressure relief devices in the accumulating condition;
L = the latent heat of vaporization of the liquid, in kJ/kg, in the accumulating condition;
M = molecular weight of the hazardous material.
Where:
cp is the specific heat at constant pressure; and
cv is the specific heat at constant volume.
C Constant Value Table
k C
1.00 0.607
1.02 0.611
1.04 0.615
1.06 0.620
1.08 0.624
1.10 0.628
1.12 0.633
1.14 0.637
1.16 0.641
1.18 0.645
1.20 0.649
1.22 0.652
1.24 0.656
1.26 0.660
1.28 0.664
1.30 0.667
1.32 0.671
1.34 0.674
1.36 0.678
1.38 0.681
1.40 0.685
1.42 0.688
1.44 0.691
1.46 0.695
1.48 0.698
1.50 0.701
1.52 0.704
1.54 0.707
1.56 0.710
1.58 0.713
1.60 0.716
1.62 0.719
Code of Federal Regulations 932
1.64 0.722
1.66 0.725
1.68 0.728
1.70 0.731
2.00 0.770
2.20 0.793
Minimum Emergency Vent Capacity
[Q Values]
AExposed area (square meters) Q(Cubic meters of air per second) AExposed area (square meters) Q(Cubic meters of air per second)
2 0.230 37.5 2.539
3 0.320 40 2.677
4 0.405 42.5 2.814
5 0.487 45 2.949
6 0.565 47.5 3.082
7 0.641 50 3.215
8 0.715 52.5 3.346
9 0.788 55 3.476
10 0.859 57.5 3.605
12 0.998 60 3.733
14 1.132 62.5 3.860
16 1.263 65 3.987
18 1.391 67.5 4.112
20 1.517 70 4.236
22.5 1.670 75 4.483
25 1.821 80 4.726
27.5 1.969 85 4.967
30 2.115 90 5.206
32.5 2.258 95 5.442
35 2.400 100 5.676
(j) Approval, inspection and testing. Approval procedures for UN portable tanks are specified in § 178.273. Inspection and testing requirements are specified in § 180.605 of this subchapter.