28.320—Fixed gas fire extinguishing systems.
(a) Requirements for vessels 79 feet (24 meters) or more in length.
A vessel 79 feet (24 meters) or more in length must be fitted with a fixed gas fire extinguishing system in the following enclosed spaces:
(b) System types and alternatives.
(1)
A pre-engineered fixed gas fire extinguishing system may be installed only in a normally unoccupied machinery space, paint locker, or space containing flammable liquid stores that has a gross volume of not more than 33.98 cubic meters (1200 cubic feet).
(2)
A fixed gas fire extinguishing system that is capable of automatic discharge upon heat detection may be installed only in a normally unoccupied space with a gross volume of not more than 169.92 cubic meters (6000 cubic feet).
(3)
A space with a gross volume exceeding 169.92 cubic meters (6000 cubic feet) must be fitted with a manually actuated and alarmed fixed gas fire extinguishing system.
(c) General requirements.
(1)
A fixed gas fire extinguishing system aboard a vessel must be approved by the Commandant and be custom engineered, unless the system meets the requirements for a pre-engineered fixed gas fire extinguishing system in paragraph (d) of this section.
(2)
System components must be listed and labeled by an independent, nationally recognized testing laboratory for the system being installed.
(3)
System design and installation must be in accordance with the Manufacturer's Marine Design, Installation, Operation, and Maintenance Manual approved for the system by the Commandant.
(4)
A fixed gas fire extinguishing system may protect more than one space. The quantity of extinguishing agent must be at least sufficient for the largest space protected by the system.
(d) Pre-engineered fixed gas fire extinguishing systems.
(1)
A pre-engineered fixed gas fire extinguishing system must:
(ii)
Be capable of manual actuation from outside the space in addition to any automatic actuation devices; and
(iii)
Automatically shut down all power ventilation systems serving the protected space and all engines that draw intake air from within the protected space.
(2)
A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station:
(iii)
A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (d)(1)(iii) of this section.
[CGD 88-079, 56 FR 40393, Aug. 14, 1991, as amended by CGD 96-046, 61 FR 57275, Nov. 5, 1996]