154.345—Air locks.
(a)
An air lock may be used for access from a gas-dangerous zone on the weather deck to a gas-safe space.
(1)
Consist of two steel doors, at least 1.5 m (4.9 ft.) but not more than 2.5 m (8.2 ft.) apart, each gasketed and tight when tested with a fire hose at not less 207 kPa gauge (30 psig);
(3)
Have an audible and visual alarm on both sides which are actuated when both door securing devices are in other than the fully closed position at the same time;
(c)
In addition to the requirements of paragraphs (a) and (b) of this section, no gas-safe space on a liquefied flammable gas carrier may have an air lock unless the space:
(1)
Is mechanically ventilated to make the pressure in the space greater than that in the air lock; and
(2)
Has a means of automatically de-energizing all electrical equipment that is not explosion-proof in the space when the pressure in the space falls to or below the pressure in the air lock.