154.1165—Controls.
(a)
Each dry chemical hand hose line must be one that can be actuated at its hose reel or hose storage cabinet.
(c)
A dry chemical monitor for the cargo loading and discharging manifold areas must be one that can be:
(2)
Except for pre-aimed monitors, controlled from a location other than the monitor and manifold area.
(d)
Each dry chemical storage unit must have independent piping with a stop valve in the piping for each remote hand hose line and remote monitor where the piping connects to the storage container, if the unit has:
(f)
Damage to any dry chemical system hose, monitor, pipe or control circuits must not prevent the operation of other hoses, monitors, or control circuit that are connected to the same storage unit.