(a) Each fire monitor of the fire main system must be fitted with a shut-off valve at the monitor and at the connection to the fire main discharge manifold required by § 132.120(h) of this part.
(b) Fire monitor piping must comply with § 132.110 of this part.
(c) Each fire monitor must be protected against over-pressure.