129.340—Cable and wiring.
(a)
If individual wires, rather than cables, are used in systems operating at a potential of greater than 50 volts, the wire and associated conduit must be run in a protected enclosure. The protected enclosure must have drain holes to prevent the buildup of condensation.
(1)
Have stranded copper conductors with sufficient current-carrying capacity for the circuit in which it is used;
(6)
Be protected by metal coverings or other suitable means, if in areas subject to mechanical abuse;
(9)
Have sheathing or wire insulation compatible with the fluid in a tank, when installed to comply with paragraph (b)(8) of this section.
(c)
Cable and wire in power and lighting circuits must be #14 AWG or larger. Cable and wire in control and indicator circuits must be #22 AWG or larger, or be ribbon cable or similar, smaller, conductor-size cable recommended by the equipment manufacturer for use in circuits for low-power instrumentation, monitoring, or control.
(1)
Comply with Section 310-13 of the NEC (NFPA 70), except that no asbestos-insulated cable or dry-location cable may be used;
(e)
Cable and wire serving vital systems listed in § 128.130(a) of this subchapter or serving emergency loads must be routed as far as practicable from areas at high risk for fire, such as galleys, laundries, and machinery spaces.
(f)
Cable or wire serving duplicated equipment must be separated so that a casualty that affects one cable does not affect the other.
(g)
Each connection to a conductor or a terminal part of a conductor must be made within an enclosure and—
(h)
A connector or lug of the set-screw type must not be used with a stranded conductor smaller than No. 14 AWG, unless there is a nonrotating follower that travels with the set screw and makes pressure contact with the conductor.
(k)
Each wire connector used in conjunction with screw-type terminal blocks must be of the captive type such as the ring or the flanged-spade type.
(iii)
A cable of large diameter or exceptional length may be spliced to facilitate its installation.
(iv)
A cable may be spliced to replace a damaged section of itself if, before replacement of the damaged section, the insulation resistance of the remainder of the cable is measured, and the condition of the insulation is unimpaired.
(m)
All material in a cable splice must be chemically compatible with other material in the splice and with the materials in the cable.
(n)
Ampacities for conductors must comply with Section 310-15 of the NEC (NFPA 70), or with IEEE Standard 45, as appropriate.
(o)
Each conductor must be sized so that the voltage drop at the load terminals does not exceed 10 percent.
(q)
Each portable or temporary electric cord or cable must be constructed and used in compliance with the requirements of § 111.60-13 of this chapter for flexible electric cord or cable.