111.97-9—Overcurrent protection.
         Overcurrent devices must be arranged to isolate a fault with as little disruption of the system as possible. The relationship between the load and the rating or setting of overcurrent devices must meet the following:
    
    
        
        (a) 
         The rating or setting of each feeder overcurrent device must be not less than 200 percent of its maximum load.
    
    
        
        (b) 
         The rating or setting of a branch circuit overcurrent device must be not more than 25 percent of that of the feeder overcurrent device.