111.30-17—Protection of instrument circuits.
(a)
Each circuit that supplies a device on a switchboard, except a circuit under paragraph (b) of this section, must have overcurrent protection.
(b)
A circuit that supplies a device on a switchboard must not have overload protection if it supplies:
(c)
If short circuit protection is used in any of the circuits listed in paragraph (b) of this section, it must be set at not less than 500% of the expected current.
(d)
A secondary circuit of a current transformer must not be fused, and the circuit from a current transformer to a device that is not in the switchboard must have a high voltage protector to short the transformer during an open circuit.