183.590—Fire test.
(1)
Fuel stop valves, “USCG Type A1” or USCG Type A2” hoses and hose clamps are tested in a fire chamber.
(2)
Fuel filters, strainers, and pumps are tested in a fire chamber or as installed on the engine in the boat.
(3)
Fuel tanks must be tested filled with fuel to one-fourth the capacity marked on the tank in a fire chamber or in an actual or simulated hull section.
(b)
Each fire test is conducted with free burning heptane and the component must be subjected to a flame for 2 1/2 minutes.
(1)
The temperature within one inch of the component must be at least 648 °C sometime during the 2 1/2 minute test;
(3)
The heptane must be in a container that is large enough to permit the perimeter of the top surface of the heptane to extend beyond the vertical projection of the perimeter of the component being tested.
(d)
If the component is being tested as installed on an engine, heptane sufficient to burn 2 1/2 minutes must be poured over the component and allowed to run into a flat bottomed pan under the engine. The pan must be large enough to permit the perimeter of the top surface of the heptane to extend beyond the vertical projection of the perimeter of the engine.
(e)
If a fuel tank is being tested in an actual or simulated hull section, the actual or simulated hull section must be of sufficient size to contain enough heptane to burn for 2 1/2 minutes in a place adjacent to the tank.