154.828—Vapor recovery and vapor destruction units.
(a)
The inlet to a vapor recovery unit which receives cargo vapor that has not been inerted, enriched, or diluted in accordance with § 154.824 of this subpart must be fitted with one of the following:
(1)
A detonation arrester;
(3)
An explosion suppression system acceptable to the Commandant (CG-522).
(b)
The inlet to a vapor destruction unit must:
(1)
Have a liquid seal; and
(2)
Have two quick-closing stop valves installed in the vapor line.
(c)
A vapor destruction unit must:
(1)
Not be within 30 meters (98.8 ft.) of any tank vessel berth or mooring at the facility;
(2)
Have a flame arrester or detonation arrester fitted in the vapor line; and
(3)
Alarm and shut down when a flame is detected on the flame arrester or detonation arrester.
(d)
When a vapor destruction unit shuts down or has a flame-out condition the vapor destruction unit control system must:
(1)
Close the quick-closing stop valves required by paragraph (b)(2) of this section; and
(2)
Close the remotely operated cargo vapor shutoff valve required by § 154.810(a) of this subpart.