149.409—How many fire extinguishers are needed?
Each particular location must have the number of fire extinguishers required by table 149.409.
Space | Classification | Minimum quantity and location |
---|---|---|
(a) Safety Areas: | ||
(1) Communicating corridors | A-II | One in each main corridor or stairway not more than 150 feet apart. |
(2) Radio room | C-II | One outside or near each radio room exit. |
(b) Accommodation Spaces: | ||
(1) Sleeping quarters | A-II | One in each sleeping space that fits more than four persons. |
(c) Service Spaces: | ||
(1) Galleys | B-II or CII | One for each 2,500 square feet or fraction thereof, for hazards involved. |
(2) Storerooms | A-II | One for each 2,500 square feet or fraction thereof, located near each exit, either inside or outside the space. |
Code of Federal Regulations
182
|
||
(3) Paint room | B-II | One outside each paint room exit. |
(d) Machinery Spaces: | ||
(1) Gas-fired boilers | B-II OR C-II | Two. |
(2) Gas-fired boilers | B-V | One. 1 |
(3) Oil-fired boilers | B-II | Two. |
(4) Oil-fired boilers | B-V | Two. 1 |
(5) Internal combustion or gas turbine engines | B-II | One for each engine. 2 |
(6) Open electric motors and generators | C-II | One for each of two motors or generators. 3 |
(e) Helicopter Areas: | ||
(1) Helicopter landing decks | B-V | One at each access route. |
(2) Helicopter fueling facility | B-V | One at each fuel transfer facility.4 |
1 Not required if a fixed system is installed. | ||
2 If the engine is installed on a weather deck or is open to the atmosphere at all times, one B-II may be used for every three engines. | ||
3 Small electrical appliances, such as fans, are exempt. | ||
4 Not required if a fixed foam system is installed in accordance with 46 CFR 108.489 . |