(a) The marine transfer area for LNG must have a ship-to-shore communication system and a separate emergency ship-to-shore communication system.
(b) Each ship-to-shore communication system must be a dedicated system that allows voice communication between the person in charge of transfer operations on the vessel, the person in charge of shoreside transfer operations, and personnel in the control room.

Code of Federal Regulations

[CGD 78-038, 53 FR 3376, Feb. 7, 1988, as amended by CGD 88-049, 60 FR 39795, Aug. 3, 1995]
(a) The marine transfer area for LHG must possess a communication system that enables continuous two way voice communication between the person in charge of transfer aboard the vessel and the person in charge of transfer for the facility.
(b) The communication system required by paragraph (a) of this section may consist either of fixed or portable telephones or of portable radios. The system must be usable and effective in all phases of the transfer and all weather at the facility.
(c) Devices used to comply with paragraph (a) of this section during the transfer of a flammable LHG must be listed as intrinsically safe by Underwriters Laboratories, Inc., Factory Mutual Research Corporation, or other independent laboratory recognized by NFPA, for use in the hazardous location in which it is used.
(a) The marine transfer area for LHG must have warning signs that—
(1) Meet paragraph (b) of this section;
(2) Can be seen from the shore and the water; and,
(3) Except as provided in paragraph (c) of this section, bear the following text:
Warning
Dangerous Cargo
No visitors
No Smoking
No Open Lights
(b) Each letter on the sign must be—
(1) In block style;
(2) Black on a white background; and
(3) At least 7.6 centimeters (3 inches) high.
(c) The words “No Smoking” and “No Open Lights” may be omitted when the product being transferred is not flammable.