77.1108-1—Type and capacity of firefighting equipment.

Firefighting equipment required under this § 77.1108 shall meet the following minimum requirements:
(a) Waterlines. Waterlines shall be capable of delivering 50 gallons of water a minute at a nozzle pressure of 50 pounds per square inch. Where storage tanks are used as a source of water supply, the tanks shall be of 1,000-gallon capacity for each 1,000 tons of coal processed (average) per shift.
(b) Fire extinguishers. Fire extinguishers shall be:
(1) Of the appropriate type for the particular fire hazard involved;
(2) Adequate in number and size for the particular fire hazard involved;
(3) Replaced immediately with fully charged extinguishers after any discharge is made from an extinguisher; and
(4) Approved by the Underwriter's Laboratories, Inc., or the Factory Mutual Research Corp., or other competent testing agency acceptable to the Mine Safety and Health Administration.
(c) Fire hose. Fire hose and couplings shall meet the requirements of the Underwriter's Laboratories, Inc., or Factory Mutual Research Corp.'s specifications. Cotton or cotton-polyester jacketed hose shall be treated in accordance with the U.S. Department of Agriculture Forest Service Specification 182 for mildew resistance. The water pressure at the hose nozzle shall not be excessively high so as to present a hazard to the nozzle operator.

Code of Federal Regulations

[36 FR 9364, May 22, 1971, as amended at 47 FR 28096, June 29, 1982]