18.24—Electrical clearances.
Minimum clearances between uninsulated electrical conductor surfaces, or between uninsulated conductor surfaces and grounded metal surfaces, within the enclosure shall be as follows:
Phase-to-Phase Voltage (rms) | Clearances (inches) | |
---|---|---|
Phase-to-Phase | Phase-to-Ground or Control Circuit | |
0 to 250 | 0.25 | 0.25 |
251 to 600 | 0.28 | 0.25 |
601 to 1000 | 0.61 | 0.25 |
1001 to 2400 | 1.4 | 0.6 |
2401 to 4160 | 3.0 | 1.4 |