434.513—Occupancy.

5131Occupancy schedules are default assumptions. The same assumptions shall be made in computing Design Energy Consumption as were used in calculating the Energy Cost Budget.
513.2Table 513.2.a, Occupancy Density, establishes the density, in ft 2 person of conditioned floor area, to be used for each building type. Table 513.2.b, Building Schedule Percentage Multipliers, establishes the percentage of total occupants in the building by hour of the day for each building type.
Table 513.2.a—Occupancy Density
Building type Conditioned floor area Ft 2 person
Assembly 50
Office 275
Retail 300
Warehouse 15000
School 75
Hotel/Motel 250
Restaurant 100
Health/Institutional 200
Multi-family High-rise Residential 2 per unit . 1
1 Heat generation: Btu/h per person: 230 Btu/h per person sensible, and 190 Btu/h per person latent. See Tables 512.2 a and b.