431.196—Energy conservation standards and their effective dates.
(a) Low-Voltage Dry-Type Distribution Transformers.
The efficiency of a low-voltage dry-type distribution transformer manufactured on or after January 1, 2007, shall be no less than that required for their kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single phase | Three phase | ||
---|---|---|---|
kVA | Efficiency (%) 1 | kVA | Efficiency (%) 1 |
15 | 97.7 | 15 | 97.0 |
25 | 98.0 | 30 | 97.5 |
37.5 | 98.2 | 45 | 97.7 |
50 | 98.3 | 75 | 98.0 |
75 | 98.5 | 112.5 | 98.2 |
100 | 98.6 | 150 | 98.3 |
167 | 98.7 | 225 | 98.5 |
250 | 98.8 | 300 | 98.6 |
333 | 98.9 | 500 | 98.7 |
750 | 98.8 | ||
1000 | 98.9 | ||
1 Efficiencies are determined at the following reference conditions: (1) for no-load losses, at the temperature of 20 °C, and (2) for load-losses, at the temperature of 75 °C and 35 percent of nameplate load. | |||
(Source: Table 4-2 of National Electrical Manufacturers Association (NEMA) Standard TP-1-2002, “Guide for Determining Energy Efficiency for Distribution Transformers.”) |
(b) Liquid-Immersed Distribution Transformers.
The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2010, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase | Three-phase | ||
---|---|---|---|
kVA | Efficiency (%) | kVA | Efficiency (%) |
10 | 98.62 | 15 | 98.36 |
15 | 98.76 | 30 | 98.62 |
25 | 98.91 | 45 | 98.76 |
37.5 | 99.01 | 75 | 98.91 |
50 | 99.08 | 112.5 | 99.01 |
75 | 99.17 | 150 | 99.08 |
100 | 99.23 | 225 | 99.17 |
167 | 99.25 | 300 | 99.23 |
250 | 99.32 | 500 | 99.25 |
333 | 99.36 | 750 | 99.32 |
500 | 99.42 | 1000 | 99.36 |
667 | 99.46 | 1500 | 99.42 |
833 | 99.49 | 2000 | 99.46 |
2500 | 99.49 | ||
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test-Procedure. 10 CFR Part 431 , Subpart K, Appendix A. |
(c) Medium-Voltage Dry-Type Distribution Transformers.
The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after January 1, 2010, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase | Three-phase | ||||||
---|---|---|---|---|---|---|---|
BILkVA | 20-45 kVefficiency(%) | 46-95 kVefficiency(%) | ≥96 kVefficiency(%) | BILkVA | 20-45 kVefficiency(%) | 46-95 kVefficiency(%) | ≥96 kVefficiency(%) |
15 | 98.10 | 97.86 | 15 | 97.50 | 97.18 | ||
25 | 98.33 | 98.12 | 30 | 97.90 | 97.63 | ||
37.5 | 98.49 | 98.30 | 45 | 98.10 | 97.86 | ||
50 | 98.60 | 98.42 | 75 | 98.33 | 98.12 | ||
75 | 98.73 | 98.57 | 98.53 | 112.5 | 98.49 | 98.30 | |
100 | 98.82 | 98.67 | 98.63 | 150 | 98.60 | 98.42 | |
167 | 98.96 | 98.83 | 98.80 | 225 | 98.73 | 98.57 | 98.53 |
250 | 99.07 | 98.95 | 98.91 | 300 | 98.82 | 98.67 | 98.63 |
333 | 99.14 | 99.03 | 98.99 | 500 | 98.96 | 98.83 | 98.80 |
500 | 99.22 | 99.12 | 99.09 | 750 | 99.07 | 98.95 | 98.91 |
667 | 99.27 | 99.18 | 99.15 | 1000 | 99.14 | 99.03 | 98.99 |
833 | 99.31 | 99.23 | 99.20 | 1500 | 99.22 | 99.12 | 99.09 |
2000 | 99.27 | 99.18 | 99.15 | ||||
2500 | 99.31 | 99.23 | 99.20 | ||||
Note: BIL means basic impulse insulation level. | |||||||
Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test- | |||||||
Procedure. 10 CFR Part 431 , Subpart K, Appendix A. |