431.134—Uniform test methods for the measurement of energy consumption and water consumption of automatic commercial ice makers.

(a) Scope. This section provides the test procedures for measuring, pursuant to EPCA, the energy use in kilowatt hours per 100 pounds of ice (kWh/100 lbs ice) and the condenser water use in gallons per 100 pounds of ice (gal/100 lbs ice).
(b) Testing and Calculations. Determine the energy consumed and the condenser water use rate of each covered product by conducting the test procedures, set forth in the Air-Conditioning and Refrigeration Institute's Standard 810-2003, “Performance Rating of Automatic Commercial Ice-Makers,” section 4, “Test Requirements,” and section 5, “Rating Requirements.” (Incorporated by reference, see § 431.133) Do not use the formula in section 8.3 of ANSI/ASHRAE Standard 29-1988 (RA 2005) for calculating the power consumption, but instead calculate the energy use rate (kWh/100 lbs Ice) by dividing the energy consumed during testing by the total mass of the ice produced during the time period over which energy consumption is measured, normalized to 100 pounds of ice as follows: